1. Environmental Advantages
No SF₆ gas Traditional ring main units commonly use SF₆ (a potent greenhouse gas), while AGi-12 uses gases with zero global warming potential (GWP), such as dry air or nitrogen, complying with environmental requirements such as the EU F-Gas regulation.
Sustainability Reduces carbon footprint and adapts to the development trend of low-carbon power grids.
2. Technical Features
Insulation Performance Environmentally friendly gases achieve insulation strength comparable to SF₆ through optimized design (such as pressure regulation and electric field equalization).
Modular Design Compact structure, supports expansion units (such as load switches, circuit breakers, metering modules), suitable for ring network, dual power supply and other topologies.
Safe and Reliable :
Fully sealed structure, IP67 protection level, dustproof and waterproof.
Built-in pressure monitoring, real-time feedback of gas status.
Three-position switch (ON, OFF, Ground) integrated with mechanical interlock to prevent misoperation.
Intelligent Options Can be equipped with sensors and communication modules (such as DTU), supporting remote monitoring (SCADA system).
3. Typical Application Scenarios
Urban Power Distribution Areas with high environmental requirements, such as residential areas and commercial centers.
Renewable Energy Integration Grid connection protection for photovoltaic and wind power plants.
Industrial Power Grids Replaces traditional SF₆ cabinets to meet corporate ESG goals.
4. Standards and Certifications
Complies with international/national standards such as IEC 62271-200 and GB/T 3906, and has passed type tests (such as temperature rise and short-circuit withstand).
5. Selection Reference
Rated Parameters 12kV/630A-1250A, 20kA short-circuit breaking capacity.
Operating Mode Manual, electric, or remote automation (optional).
Environmental Adaptability Wide temperature operation range: -25℃~+40℃.
6. Market Positioning
Suitable for areas that need to meet stringent environmental regulations (such as Europe and first-tier cities in China), or power projects pursuing green transformation.
For more detailed technical parameters or cases, please provide specific needs (such as configuration list or application scenarios).